Concentrations of Polychlorinated Biphenyls in Soil and Indoor Dust Associated with Electricity Generation Facilities in Lagos, Nigeria.

dc.contributor.authorFolarin, B.T.
dc.contributor.authorAbdallah, M.A.
dc.contributor.authorOluseyi, T.O.
dc.contributor.authorOlayinka, K.O.
dc.contributor.authorHarrad, S.
dc.date.accessioned2019-09-03T14:21:31Z
dc.date.available2019-09-03T14:21:31Z
dc.date.issued2018
dc.descriptionStaff publicationsen_US
dc.description.abstractConcentrations of 7 indicator polychlorinated biphenyls (PCBs) were measured in dust and soil samples from 12 power stations collected over the two major seasons of the Nigerian climate. Median ƩPCB7 concentrations in soil ranged from 2 ng/g for power station A to 220 ng/g for power station I; while those in dust ranged from 21 ng/g for power station L to 2200 ng/g for power station I. For individual congeners, median PCB concentrations ranged from 3.8 ng/g for PCB 101 to 52 ng/g for PCB 180 in dust, and <0.07 ng/g for PCB 28 to 5.9 ng/g for PCB 153 in soil. The type of power station activity exerted a significant influence on concentrations of ΣPCB7 in dust and soil (generation > transmission > distribution). Congener patterns in dust and soil samples were compared using principal component analysis (PCA) with those in transformer oil samples from 3 of the power stations studied and with common PCB mixtures (Aroclors). This revealed congener patterns in soil were more closely related to that in the transformer oil than dust. Congener patterns in most samples were similar to Aroclor 1260. Concentrations of PCBs in soil samples close to the transformers significantly exceeded those in soil sampled further away.en_US
dc.identifier.citationFolarin, B. T. [Et...al]. (2018). Concentrations of polychlorinated biphenyls in soil and indoor dust associated with electricity generation facilities in Lagos, Nigeria. Chemosphere, vol.207, 620-625pp.en_US
dc.identifier.urihttps://ir.unilag.edu.ng/handle/123456789/5108
dc.language.isoenen_US
dc.publisherElsevieren_US
dc.subjectPCBsen_US
dc.subjectPower generation plantsen_US
dc.subjectAfricaen_US
dc.subjectTransformersen_US
dc.subjectResearch Subject Categories::NATURAL SCIENCES::Chemistryen_US
dc.titleConcentrations of Polychlorinated Biphenyls in Soil and Indoor Dust Associated with Electricity Generation Facilities in Lagos, Nigeria.en_US
dc.typeArticleen_US
Files
Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
12. Concentrations of PCBs in soil and indoor dust associated with electricity generation.pdf
Size:
563.98 KB
Format:
Adobe Portable Document Format
Description:
License bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed upon to submission
Description: